VESDA Laser Focus (VLF-250)

VESDAVESDA Laser Focus (VLF-250)

Very Early Smoke Detection Apparatu
High-sensitivity air intake sensing

VESDA VESDA Laser Focus (VLF-250)
Type approval 11-30 (Analog type, 1 air intake input, air pipe maximum length 25m)
Surrounding
temperature
0 ~ 39℃ color Gray
Relative humidity 0 ~ 95% Size 225(W) X 185(H) X 90(D)mm
Rated voltage DC 24V IP rating 30
Current consumption surveillance 250mA / alert 295mA Weight 2.0kg
Sensing method method where the air intake pipe sucks in smoke particles, and measures how much light is scattered at the laser chamber) Attached materials VSP-005(Filter)
Range of sensitivity 0.025 ~ 20% obs/m Threshold
value set range
alert, action 0.025% ~ 2.00% obs/m
Fire1, Fire2 0.025% ~ 20.00% obs/m

※ VLF-250 / Laser Focus Detector can install one air intake pipe. (Two pieces are possible through the accessory material)

VESDA Overview

Real-time measurement of "current smoke concentration in the air" using a pipe network "Active" early detection of signs of fire Early detection of smoke.

VESDA Features

  • Optical Light Scattering detection method using laser (Absolute value detection of smoke)
  • System auto-configuration function (Autolearn)
  • World's highest sensitivity detection and maximum sensing range (0.00075 ~ 32% obs / m)
  • The world's largest event can be stored (18,000)
  • World's highest / maximum range fire alarm value (0.005-20% obs / m)
  • Automatic fault diagnosis
  • Dust filter using dual filter
  • The optical part is kept clean and no correction is required
  • Always detect air flow per pipe
  • VESDANET communication enables monitoring and control in any area

VESDA certification

Comparing VESDA and existing fire detectors
Division Existing fire detector
General detector Analog detector
Sensitivity (%/m) 4 to 10 (% / m) 3 to 8 (% / m) 0.005 (% / m)
Fine smoke detection X X X
Alarm classification Simple alarm Multi-level (2) Alarm Multi-level (3 ~ 4) Alarm
Data Management No function No function Data storage Data storage, transmission Data storage, transmission
Environmental conditions (high / low temperature) Influence Influence Influence Influence Influence Influence
Equipment life 5 to 10 years 5 to 10 years More than 10 years
Fire Alarm Point General Location: Fire Progress Stage General Places: Fire Progress Stage General Places: Early Stage of Fire
Air-conditioning system: Fire spreading stage Air-conditioning system: Fire spreading stage Air-conditioning system: Early stage of fire
Maintenance 5 ~ 10 years Failure check failure Failure Self diagnosis
Automatic environment calibration technology X X Notify operator of dust, humidity, air flow, etc.
Adjust sensitivity depending on environment X X Adjustment of random sensitivity according to the application place of clean room, factory, etc.
Adjust sensitivity depending on environment X X Sensitivity can be set according to day / night environment